PI VISION MAQS VOLUME CALCULATION SYNTAX — CURRENT DASHBOARD PARITY ====================================================== Purpose ------- Copy/paste mapping for PI Vision display calculation boxes. Proven dashboard corrections are included. PI Vision cannot reproduce the dashboard's persisted signed five-hour/last-known-good fallback chain in a single text-box expression; the PI expressions therefore retain visible engineering defaults, while the dashboard remains the operational parity authority during bad/zero telemetry. CALCULATION_NAME: TOTAL FAL 1SH SYNTAX: Concat((if 'MAQ.10.AF.Volume'=0 then 45 else 'MAQ.10.AF.Volume') + (if 'MAQ.11.AF.Volume'=0 then 140 else 'MAQ.11.AF.Volume') + (if 'MAQ.4.AF.Volume'=0 then 150 else 'MAQ.4.AF.Volume')," m3/s",if ('MAQ.10.AF.Volume'=0) or ('MAQ.11.AF.Volume'=0) or ('MAQ.4.AF.Volume'=0) then "(engineering default used)" else " ") PARITY_TARGET: Underground working total; no 1.12 density factor. Dashboard substitutes signed 5h/retained averages before these engineering defaults. CALCULATION_NAME: TOTAL 2 SH SYNTAX: Concat((if 'MAQ.34.AF.Volume'=0 then 175 else 'MAQ.34.AF.Volume') + (if 'MAQ.35.AF.VOL'=0 then 205 else 'MAQ.35.AF.VOL') + (if 'MAQ.43.AF.Volume'=0 then 44 else 'MAQ.43.AF.Volume') + (if 'MAQ.12.AF.Volume'=0 then 210 else 'MAQ.12.AF.Volume') + (if 'MAQ.14.AF.Volume'=0 then 175 else 'MAQ.14.AF.Volume') + 180 + 60," m3/s",if ('MAQ.34.AF.Volume'=0) or ('MAQ.35.AF.VOL'=0) or ('MAQ.43.AF.Volume'=0) or ('MAQ.12.AF.Volume'=0) or ('MAQ.14.AF.Volume'=0) then "(engineering default used)" else " ") PARITY_TARGET: Underground 2 Shaft total including confirmed SH02-SX02 +180 and SH05-VD05 +60 allowances; no standalone density factor. CALCULATION_NAME: SH3 UG Total SYNTAX: Concat((if 'MAQ.68.AF.Volume'=0 then 180 else 'MAQ.68.AF.Volume') + (if 'MAQ.46.AF.Volume'=0 then 155 else 'MAQ.46.AF.Volume') + (if 'MAQ.76.AF.VOL'=0 then 340 else 'MAQ.76.AF.VOL') + (if 'MAQ.77.AF.Volume'=0 then 118 else 'MAQ.77.AF.Volume') + (if 'MAQ.71.AF.Volume'=0 then 85 else 'MAQ.71.AF.Volume')," m3/s",if ('MAQ.68.AF.Volume'=0) or ('MAQ.46.AF.Volume'=0) or ('MAQ.76.AF.VOL'=0) or ('MAQ.77.AF.Volume'=0) or ('MAQ.71.AF.Volume'=0) then "(fixed number used)" else " ") PARITY_TARGET: Summed underground 3 Shaft MAQS total used by the dashboard validation. CALCULATION_NAME: SH3 Total SYNTAX: Concat((if 'MAQ.94.AF.Volume'=0 then 900 else 'MAQ.94.AF.Volume') * 1.12," m3/s",if ('MAQ.94.AF.Volume'=0) then "(fixed number used)" else " ") PARITY_TARGET: Independent MAQS 94 underground reference converted to surface equivalent with whole-total ×1.12. CALCULATION_NAME: Total Intake SYNTAX: Concat(((if \'MAQ.34.AF.Volume\'=0 then 133 else \'MAQ.34.AF.Volume\') + (if \'MAQ.35.AF.VOL\'=0 then 210 else \'MAQ.35.AF.VOL\') + (if \'MAQ.43.AF.Volume\'=0 then 44 else \'MAQ.43.AF.Volume\') + (if \'MAQ.12.AF.Volume\'=0 then 210 else \'MAQ.12.AF.Volume\') + (if \'MAQ.14.AF.Volume\'=0 then 175 else \'MAQ.14.AF.Volume\') + (if \'MAQ.94.AF.Volume\'=0 then 1080 else \'MAQ.94.AF.Volume\') + (if \'MAQ.10.AF.Volume\'=0 then 25 else \'MAQ.10.AF.Volume\') + (if \'MAQ.11.AF.Volume\'=0 then 220 else \'MAQ.11.AF.Volume\') + (if \'MAQ.4.AF.Volume\'=0 then 125 else \'MAQ.4.AF.Volume\')) + (if 'MAQ.35.AF.VOL'=0 then 205 else 'MAQ.35.AF.VOL') + (if 'MAQ.43.AF.Volume'=0 then 44 else 'MAQ.43.AF.Volume') + (if 'MAQ.12.AF.Volume'=0 then 210 else 'MAQ.12.AF.Volume') + (if 'MAQ.14.AF.Volume'=0 then 175 else 'MAQ.14.AF.Volume') + (if 'MAQ.68.AF.Volume'=0 then 180 else 'MAQ.68.AF.Volume') + (if 'MAQ.76.AF.VOL'=0 then 340 else 'MAQ.76.AF.VOL') + (if 'MAQ.46.AF.Volume'=0 then 155 else 'MAQ.46.AF.Volume') + (if 'MAQ.77.AF.Volume'=0 then 118 else 'MAQ.77.AF.Volume') + (if 'MAQ.10.AF.Volume'=0 then 45 else 'MAQ.10.AF.Volume') + (if 'MAQ.11.AF.Volume'=0 then 140 else 'MAQ.11.AF.Volume') + (if 'MAQ.4.AF.Volume'=0 then 150 else 'MAQ.4.AF.Volume') + 180 + 60) * 1.12," m3/s",if ('MAQ.34.AF.Volume'=0) or ('MAQ.35.AF.VOL'=0) or ('MAQ.43.AF.Volume'=0) or ('MAQ.12.AF.Volume'=0) or ('MAQ.14.AF.Volume'=0) or ('MAQ.68.AF.Volume'=0) or ('MAQ.76.AF.VOL'=0) or ('MAQ.46.AF.Volume'=0) or ('MAQ.77.AF.Volume'=0) or ('MAQ.10.AF.Volume'=0) or ('MAQ.11.AF.Volume'=0) or ('MAQ.4.AF.Volume'=0) then "(engineering default used)" else " ") PARITY_TARGET: Complete Shafts 1/2/3 intake including +180/+60 allowances, then whole-total ×1.12 surface correction. CALCULATION_NAME: 4SHAFTOTAL SYNTAX: Concat((if 'MAQ.75.AF.Volume'=0 then 320 else 'MAQ.75.AF.Volume') + (if 'MAQ.73.AF.Volume'=0 then 320 else 'MAQ.73.AF.Volume') + (if 'MAQ.91.AF.Volume'=0 then 347 else 'MAQ.91.AF.Volume') + (if 'MAQ.92.AF.Volume'=0 then 376 else 'MAQ.92.AF.Volume')," m3/s",if ('MAQ.75.AF.Volume'=0) or ('MAQ.73.AF.Volume'=0) or ('MAQ.91.AF.Volume'=0) or ('MAQ.92.AF.Volume'=0) then "(engineering default used)" else " ") PARITY_TARGET: Underground 4 Shaft working total; ×1.12 is applied only when rolled into the surface-equivalent combined total. CALCULATION_NAME: 2SHOUTS SYNTAX: Concat((if 'MAQ.37.AF.Volume'=0 then 150 else 'MAQ.37.AF.Volume') + (if 'MAQ.1.AF.Volume'=0 then 215 else 'MAQ.1.AF.Volume') + (if 'MAQ.2.AF.Volume'=0 then 200 else 'MAQ.2.AF.Volume') + (if 'MAQ.55.AF.Volume'=0 then 182 else 'MAQ.55.AF.Volume') + 60," m3/s",if ('MAQ.37.AF.Volume'=0) or ('MAQ.1.AF.Volume'=0) or ('MAQ.2.AF.Volume'=0) or ('MAQ.55.AF.Volume'=0) then "(engineering default used)" else " ") PARITY_TARGET: Underground 5 Shaft upcast including SH05-VD05 +60; no standalone density factor. CALCULATION_NAME: 4&5SHAFTTOTAL SYNTAX: Concat(((if 'MAQ.75.AF.Volume'=0 then 320 else 'MAQ.75.AF.Volume') + (if 'MAQ.73.AF.Volume'=0 then 320 else 'MAQ.73.AF.Volume') + (if 'MAQ.91.AF.Volume'=0 then 347 else 'MAQ.91.AF.Volume') + (if 'MAQ.92.AF.Volume'=0 then 376 else 'MAQ.92.AF.Volume') + (if 'MAQ.37.AF.Volume'=0 then 150 else 'MAQ.37.AF.Volume') + (if 'MAQ.1.AF.Volume'=0 then 215 else 'MAQ.1.AF.Volume') + (if 'MAQ.2.AF.Volume'=0 then 200 else 'MAQ.2.AF.Volume') + (if 'MAQ.55.AF.Volume'=0 then 182 else 'MAQ.55.AF.Volume') + 60) * 1.12," m3/s",if ('MAQ.75.AF.Volume'=0) or ('MAQ.73.AF.Volume'=0) or ('MAQ.91.AF.Volume'=0) or ('MAQ.92.AF.Volume'=0) or ('MAQ.37.AF.Volume'=0) or ('MAQ.1.AF.Volume'=0) or ('MAQ.2.AF.Volume'=0) or ('MAQ.55.AF.Volume'=0) then "(engineering default used)" else " ") PARITY_TARGET: Complete 4/5 Shaft underground upcast including +60, then whole-total ×1.12 surface correction. This fixes the old 1.08 scope error. CALCULATION_NAME: C2S intake SYNTAX: Concat((if 'MAQ.68.AF.Volume'=0 then 180 else 'MAQ.68.AF.Volume') - (if 'MAQ.61.AF.Volume'=0 then -65 else 'MAQ.61.AF.Volume')," m3/s",if ('MAQ.68.AF.Volume'=0) or ('MAQ.61.AF.Volume'=0) then "(fixed number used)" else " ") PARITY_TARGET: Algebraically clean equivalent of the current double-negative expression with dashboard Fixed Numbers; signed airflow is retained. CALCULATION_NAME: C2S Return SYNTAX: (if 'MAQ.28.AF.Volume'=0 then -8 else 'MAQ.28.AF.Volume') + (if 'MAQ.74.AF.VOL'=0 then -55 else 'MAQ.74.AF.VOL') + (if 'MAQ.60.AF.Volume'=0 then 47 else 'MAQ.60.AF.Volume') + ((if 'MAQ.68.AF.Volume'=0 then 180 else 'MAQ.68.AF.Volume') - ((if 'MAQ.62.AF.VOL'=0 then 65 else 'MAQ.62.AF.VOL') + (if 'MAQ.63.AF.VOL'=0 then -57 else 'MAQ.63.AF.VOL') + (if 'MAQ.28.AF.Volume'=0 then -8 else 'MAQ.28.AF.Volume') + (if 'MAQ.74.AF.VOL'=0 then -55 else 'MAQ.74.AF.VOL'))) PARITY_TARGET: Current PI expression with dashboard Fixed Numbers. MAQ.28 and MAQ.74 still algebraically cancel; engineering intent remains unresolved, so do not simplify the circuit expression. CURRENT FIXED NUMBER REGISTER (GENERATED) ========================================= Generated: 2026-07-17T07:04:30 These are the dashboard's current password-protected Fixed Numbers. Formula entries above are refreshed from this register when applicable. MAQ.1.AF.Volume = 215 m3/s MAQ.10.AF.Volume = 45 m3/s MAQ.11.AF.Volume = 140 m3/s MAQ.12.AF.Volume = 210 m3/s MAQ.14.AF.Volume = 175 m3/s MAQ.2.AF.Volume = 200 m3/s MAQ.28.AF.Volume = -8 m3/s MAQ.34.AF.Volume = 175 m3/s MAQ.35.AF.VOL = 205 m3/s MAQ.37.AF.Volume = 150 m3/s MAQ.4.AF.Volume = 150 m3/s MAQ.43.AF.Volume = 44 m3/s MAQ.46.AF.Volume = 155 m3/s MAQ.55.AF.Volume = 182 m3/s MAQ.60.AF.Volume = 47 m3/s MAQ.61.AF.Volume = -65 m3/s MAQ.62.AF.VOL = 65 m3/s MAQ.63.AF.VOL = -57 m3/s MAQ.68.AF.Volume = 180 m3/s MAQ.71.AF.Volume = 85 m3/s MAQ.73.AF.Volume = 320 m3/s MAQ.74.AF.VOL = -55 m3/s MAQ.75.AF.Volume = 320 m3/s MAQ.76.AF.VOL = 340 m3/s MAQ.77.AF.Volume = 118 m3/s MAQ.91.AF.Volume = 347 m3/s MAQ.92.AF.Volume = 376 m3/s MAQ.94.AF.Volume = 900 m3/s SH02-SX02 = 180 m3/s SH05-VD05 = 60 m3/s